Search
Close this search box.

IWF with busbar 20×5

CONSTRUCTION AND APPLICATION:

The IWF transformers are made as single-phase, low voltage, indoor, dry transformers on a ring core, intended to supply measuring instruments with the maximum permissible operating voltage below 0.72 kV and a frequency of 50 Hz. The IWF transformers are designed to be mounted on a current circuit bus through primary terminals of the 20×5* transformer. In addition, they can be installed on a TS 35 -35×7.5 mounting rail (as per EN 50022, BS 5584 or DIN 46277-3) or fixed to the ground via sleeve joints with Ø 5.4 openings, which are provided as part of the transformer delivery.

The transformer secondary current is 5A.

The Current Transformers meet the requirements of PN-EN 61869-1:2009  i PN-EN 61869-2:2013-06 European Standards.

ll current transformers manufactured by F.A.E. „FANINA” S.A. are calibrated by the company laboratory, and the calibration costs are included in the price of the product. Additionally, at the Client’s request, we provide current transformers calibrated by the Regional Weights and Measures Office orcalibratedby the accredited PCA laboratory (extra charge)

TECHNICAL DATA:

Rated frequency f = 50 Hz
Maximum permissible voltage of the device Um = 0.72 kV
Rated test voltage with a power-line frequency: 3 kV
Insulation class: B
Extended current range: 120%
Rated short-term thermal current lth = 60 x lpr
Rated dynamic current Idyn = 2,5 x Ith
Casing: HB glass fibre reinforced self-extinguishing polyamide (acc. to UL-94)
Operating temperature: -35 ÷ + 55°C
Degree of protection: IP20, IK07
Product in conformance with the provisions of directive – LVD 2014/35/UE for executions exceeding 50VAC.

Current

Ipn/Isn

Short-term rated current (Ith)

Rated peak current

(Idyn)

class 0.5

class 0.2

class 0.5s

class 0.2s

Mounting dimensions

Power Sn

FS

Power Sn

FS

Power Sn

FS

Power Sn

FS

A/A

(kA)

(kA)

(VA)

(VA)

(VA)

(VA)

(mm)

30/5

60 x Ipn

150 x Ipn

2,5; 5; 10

5

2,5; 5

5

2,5; 5

5

2,5; 5

5

TS35 35×7,5

(acc EN 50022, BS 5584 or DIN 46277/3)

or

58×90

or

84×66

50/5

2,5; 5; 10

5

2,5; 5

5

2,5; 5

5

2,5; 5

5

75/5

2,5; 5; 10

5

2,5; 5

5

2,5; 5

5

2,5; 5

5

100/5

2,5; 5; 10

5

2,5; 5

5

2,5; 5

5

2,5; 5

5

125/5

2,5; 5; 10

5

2,5; 5

5

2,5; 5

5

2,5; 5

5

150/5

2,5; 5; 10

5

2,5; 5

5

2,5; 5

5

2,5; 5

5

200/5

2,5; 5; 10

5

2,5; 5

5

2,5; 5

5

2,5; 5

5

250/5

2,5; 5; 10

5

2,5; 5

5

2,5; 5

5

300/5

2,5; 5; 10

5

2,5; 5

5

2,5; 5

5

400/5

2,5; 5; 10

5

2,5; 5

5

2,5; 5

5

2,5; 5

5

If the presented product is close to your requirements, but does not quite meet them – please contact us. Today most of our products are created in cooperation with our clients.